Ten motel PTACs cost $673 to $1,424 each, and the cheapest heat pumps are as efficient as any we priced

Beige through-the-wall PTAC unit under a window sill, its control flap open and the display lit in cool mode
A packaged terminal air conditioner installed under a window in an apartment, with its control panel open. Photo: “Packaged terminal air conditioner” by Central Avenue, CC BY 4.0, via Wikimedia Commons, resized.

PTAC units for hotels, the through-the-wall heaters and air conditioners that the Department of Energy (DOE) models in small hotel guest rooms, cost $672.98 to $1,424.26 each at PTAC4Less, a national online dealer, when we priced ten 12,000 Btu/h models on Oct 21, 2026 [1][2][3].

For a 30-room motel replacing every unit at once, that is $20,750 for 30 Genuine Comfort heat pumps at the dealer’s 30-unit price, or $40,592 for 30 Amana heat pumps, before sleeves, grilles and labor [4][3]. Eight years of cooling power for the same rooms costs about as much again, as the math below shows.

We priced them the way an owner replacing a whole building would: one size, one voltage, one dealer, one day, then the federal efficiency rules and the power bill. Motel4 publishes this post and sells an AI phone receptionist. We sell no air conditioners and have no tie to any brand or dealer named here.

How we research and check posts like this one is on how we write.

Prices, checked Oct 21, 2026

The table lists the ten models cheapest first, with the dealer’s single-unit price and its per-unit price on an order of 30 or more. Each product page says the price covers the unit alone: “Sleeve Included: No Grille Included: No” [4].

ModelHeatEER1 unit30+ units, eachSource
Midea MP12HMB32 (out of stock)Heat pump11.6$672.98$639.33[2]
Genuine Comfort GC42E-H12KC3-3Heat pump11.6$728.08$691.68[4]
Hotpoint AHHS12D3XXAHeat pump10.4/10.5$814.54$773.81[5]
Distinctions DCP123J35BAElectric heat10.7$881.14$837.08[6]
Friedrich PZH12K3SCHeat pump10.6$1,148.16not listed[7]
Amana PTC123J35AXXXElectric heat11.5$1,171.37$1,112.80[8]
Friedrich PDE12K3SGR3Electric heat11.6$1,275.37not listed[9]
GE Zoneline AZHS12DCXXAHeat pump11.6$1,279.03$1,215.08[10]
Friedrich PDH12K3SGR3Heat pump11.6$1,301.15not listed[11]
Amana PTH123J35AXXXHeat pump11.5$1,424.26$1,353.05[3]

On the seven models with a volume price, an order of 30 or more takes 5 percent off. The three Friedrich listings show no volume price [7][9][11].

The cheapest unit was not for sale that day. The Midea page read “Quantity: Out of stock,” which made the Genuine Comfort at $728.08 the cheapest heat pump you could order [2][4].

The cheapest PTAC units for hotels match the best efficiency listed

On this list, paying more does not buy a lower power bill. EER, the energy efficiency ratio, is cooling output in Btu per hour for each watt drawn, so a higher number means less electricity for the same cooling [12].

The Genuine Comfort is rated EER 11.6, the same as the GE Zoneline, which costs $550.95 more [4][10]. The Friedrich PDH12K3SGR3 and PDE12K3SGR3 are also 11.6 [9][11]. The most expensive unit, the Amana heat pump, is rated 11.5 [3].

Paying more on this list bought neither better efficiency nor a longer compressor warranty. The cheapest orderable unit, the Genuine Comfort, lists a 1-year labor warranty and a 6-year compressor and sealed-system warranty, the longest compressor term of any unit that lists one; the dearer GE Zoneline and Amana heat pump list 1 year and 5 years [4][10][3]. The one longer labor warranty on the list is the Friedrich PZH12K3SC’s 2 years, at $1,148.16 [7]. What’s left is controls and brand.

Controls differ too. Both Amana units are listed with external thermostat controls, and the heat pump’s page says it “Requires installation of a Wall Thermostat (Sold Separately)” [3]. Budget one per room if you pick either Amana.

Each of the ten product pages reads “Energy Star Certified: No” [4]. Among units with the same heat type, that leaves warranty, controls, brand and price as the differences.

The federal floor matters most for old, small wall sleeves

The efficiency floor a unit must meet depends on the hole in your wall. Under 10 CFR 431.92, a standard-size unit fits a wall opening at least 16 inches high or at least 42 inches wide, with a cross-section of at least 670 square inches. A non-standard unit fits an existing sleeve smaller than that [12].

For a 12,000 Btu/h standard-size air conditioner made since January 1, 2017, the floor is 14.0 minus 0.3 times the capacity in thousands of Btu/h, which works out to EER 10.4. A non-standard air conditioner’s floor is 10.9 minus 0.213 times capacity, or EER 8.344; a non-standard heat pump’s floor is 10.8 minus 0.213 times capacity, or EER 8.244 [13].

At those floors, a non-standard air conditioner uses about 24.6 percent more electricity than the standard floor for the same cooling, about $330 more per room over 8 years at the middle case in the math below. A non-standard heat pump uses about 26.2 percent more, about $351 more per room over 8 years, since seven of the ten units priced are heat pumps [13][14].

Old buildings are the norm in this trade. DOE notes that in its 2018 Commercial Buildings Energy Consumption Survey, 80 percent of lodging buildings that use an individual room air conditioner were built before 2000 [1]. In 2023 DOE kept the floors unchanged, saying it lacked “clear and convincing evidence” that tighter standards would save significant additional energy and be technologically feasible and economically justified [1].

So measure the wall sleeve opening first. All ten units in the table are listed as fitting the standard 42-inch by 16-inch sleeve; a smaller opening means a non-standard chassis or a new sleeve, cut into a larger opening [4].

Then match the volts and amps. Nine of the ten use a NEMA 6-20 plug on a 208/230-volt, 20-amp supply; the GE Zoneline’s amps and plug are listed as “Universal” [4][10]. Check the nameplate and the receptacle on the unit you are replacing before you order 30 of anything.

Flowchart: measure the wall sleeve opening, check its size, match the volts and amps, choose heat pump or electric heat, then order in volume
The checks to make before ordering replacement PTACs, from the wall sleeve to the heat type. Diagram: Motel4.

Heat pump or electric heat: your winter decides

A heat pump PTAC heats by running its refrigeration cycle in reverse and keeps a backup heat source, under the federal definition [12]. An electric-heat unit turns each kilowatt-hour into one kilowatt-hour of heat.

The Amana heat pump is rated at a coefficient of performance (COP) of 3.3, so at that rating it delivers 1,000 kWh of heat for about 303 kWh of electricity [3]. Against the electric-heat Amana, that saves about 697 kWh, or $101.27 at the July 2026 U.S. commercial price of 14.53 cents per kWh [14].

The Amana heat pump costs $252.89 more than its electric-heat twin, so it pays back after about 2,497 kWh of heat, the output of its 3.5 kW backup heater running flat out for about 713 hours [3][8]. The Friedrich pair is closer: the heat pump costs $25.78 more and pays back after about 251 kWh [9][11].

The rated COP comes from a standard test, and real winters differ, so treat these paybacks as the best case.

Cooling 30 rooms for eight years costs about $36,074 at U.S. prices

The worked example prices cooling only, for 30 rooms at EER 11.6 over DOE’s 8-year average life [1]. The 1,000 full-load cooling hours a year is our assumption, and the power price is the July 2026 U.S. commercial average [14].

That is about $36,074, more than the $20,750 for 30 Genuine Comfort units and close to the $36,452 for 30 GE Zoneline units at the 30-unit price [4][10].

Your number depends far more on climate and power price than on the model. Pick the row for your cooling hours and the column nearest your power price:

Full-load cooling hours a yearTexas, 8.47 centsU.S. average, 14.53 centsCalifornia, 30.56 cents
500$10,514$18,037$37,937
1,000$21,029$36,074$75,873
2,000$42,058$72,149$151,746

Efficiency moves the total far less. Going from the federal floor of EER 10.4 to 11.6 saves about 119 kWh per room a year at 1,000 hours, or $138.75 per room over 8 years at the U.S. price. For 30 rooms that is $4,162 [13][14].

Stacked bars for ten PTAC models: unit price plus eight years of cooling power, totals from $1,875 to $2,637 per room
Over eight years, cooling power adds $1,202 to $1,341 per room, while unit prices run from $672.98 to $1,424.26. Chart: Motel4. Data: PTAC4Less product pages, EIA Electric Power Monthly table 5.6.A, DOE, unit price plus 8 years of cooling power for ten 12,000 Btu/h PTACs, prices Oct 21, 2026; power price July 2026.

To be fair, this is one dealer on one day, and the math leaves out heating, sleeves, grilles, installation and repairs. We could not confirm failure rates or parts availability by brand; none of our sources publishes them. DOE’s 8-year life is an average, and its analysis allows for units lasting up to 16 years [1].

Verdict

Pick the Genuine Comfort, or another EER 11.6 heat pump near the bottom of the price table, if your sleeves are standard size; on this list the extra $550.95 for a GE Zoneline buys no efficiency and no longer compressor warranty [4][10]. Pay more only if the Friedrich PZH12K3SC’s longer labor warranty, a specific control setup, or brand is worth it to you [7].

Choose a heat pump over electric heat if your rooms need real heat in winter: the Amana premium is repaid after about 2,497 kWh of heat, the Friedrich premium after about 251 kWh. Choose electric heat only if winters are mild and the price gap is large.

If your openings are under 670 square inches, price non-standard chassis or new sleeves before anything else, because that choice sets your floor at EER 8.344 for an air conditioner, or 8.244 for a heat pump, instead of 10.4 [13][12].

When a unit dies in July, the guest calls the front desk first. Our notes on handling complaint calls cover what to say while the replacement ships.

How we did this

Search demand from Google Keyword Planner (US, pulled Oct 21, 2026). Prices, ratings and warranties from ten PTAC4Less product pages, checked Oct 21, 2026. Efficiency floors from 10 CFR 431.92 and 431.97, unit life from DOE's Feb 13, 2023 final determination, and power prices from EIA's Electric Power Monthly table 5.6.A for July 2026, all accessed Oct 21, 2026. Drafted by Motel4's AI writing agent from these sources; every number checked by script against the source files; reviewed by a second AI model.

Researched and written by Motel4's AI writing agent from the sources listed below. Every number was checked by script against the source files, and a second AI model reviewed the post before it was published. The Motel4 Team is responsible for this page.

Sources

  1. U.S. Department of Energy, Federal Register, Energy conservation standards for packaged terminal air conditioners and heat pumps: final determination, Feb 13, 2023 (primary source), accessed Oct 21, 2026.
  2. PTAC4Less, Midea MP12HMB32 12,000 BTU PTAC, 208/230 V, heat pump: product page (primary source), accessed Oct 21, 2026.
  3. PTAC4Less, Amana PTH123J35AXXX 12,000 BTU PTAC, 208/230 V, heat pump: product page (primary source), accessed Oct 21, 2026.
  4. PTAC4Less, Genuine Comfort GC42E-H12KC3-3 12,000 BTU PTAC, 208/230 V, heat pump: product page (primary source), accessed Oct 21, 2026.
  5. PTAC4Less, Hotpoint AHHS12D3XXA 12,000 BTU PTAC, 208/230 V, heat pump: product page (primary source), accessed Oct 21, 2026.
  6. PTAC4Less, Distinctions DCP123J35BA 12,000 BTU PTAC, 208/230 V, electric heat: product page (primary source), accessed Oct 21, 2026.
  7. PTAC4Less, Friedrich PZH12K3SC 12,000 BTU PTAC, 208/230 V, heat pump: product page (primary source), accessed Oct 21, 2026.
  8. PTAC4Less, Amana PTC123J35AXXX 12,000 BTU PTAC, 208/230 V, electric heat: product page (primary source), accessed Oct 21, 2026.
  9. PTAC4Less, Friedrich PDE12K3SGR3 12,000 BTU PTAC, 208/230 V, electric heat: product page (primary source), accessed Oct 21, 2026.
  10. PTAC4Less, GE Zoneline AZHS12DCXXA 12,000 BTU PTAC, 208/230 V, heat pump: product page (primary source), accessed Oct 21, 2026.
  11. PTAC4Less, Friedrich PDH12K3SGR3 12,000 BTU PTAC, 208/230 V, heat pump: product page (primary source), accessed Oct 21, 2026.
  12. Electronic Code of Federal Regulations, National Archives, 10 CFR 431.92, Definitions concerning commercial air conditioners and heat pumps (primary source), accessed Oct 21, 2026.
  13. Electronic Code of Federal Regulations, National Archives, 10 CFR 431.97, Energy efficiency standards and their compliance dates (primary source), accessed Oct 21, 2026.
  14. U.S. Energy Information Administration, Electric Power Monthly, Table 5.6.A: Average price of electricity to ultimate customers by end-use sector, by state, July 2026 and 2025 (primary source), accessed Oct 21, 2026.

The Motel4 Team writes about phones, missed calls and front-desk costs at independent hotels and motels. Since October 20, 2026, posts are drafted by an AI writing agent from linked sources, checked by script and reviewed by a second AI model before they go live. How we write. To reach us or report an error: motel4.ai/contact.